PORT-A-COOL®Series 2000OWNERS MANUALfor Hazardous Location UnitsU.S. Patent 6,223,548U.S. Patent D 362,905U.S. Patent 6,502,414FOR ELECTRIC MODELSPAC2
PORT-A-COOL® Hazardous Location Units*CAUTION - DO NOT LEAVE PRIME VALVE ON OR THE UNIT MAY FLOOD!When initially turning on the pump, the level in t
PORT-A-COOL® Hazardous Location Units*Ill. MAINTENANCE & STORAGEVery little maintenance is actually required on the PORT-A-COOL® unit. The prima
PORT-A-COOL® Hazardous Location Units*V. TROUBLESHOOTING / REPAIRA. TroubleshootingThe most common problems encountered with a PORT-A-COOL® unit ar
PORT-A-COOL® Hazardous Location Units*FAN SYSTEMBELT DRIVE MODELS CAUTIONPlease use caution when troubleshooting or repairing all electrical compo-n
PORT-A-COOL® Hazardous Location Units*WATER SYSTEMThe water system consists of three primary elements: 1) Water Delivery System, 2) Spray Bar Assemb
PORT-A-COOL® Hazardous Location Units*PLUMBING ASSEMBLY SPRAY BAR ASSEMBLY (ALL MODELS) BRONZE PUMP (PAC2K36EP and PAC2K48EP Only) PROBLEM CHECK
PORT-A-COOL® Hazardous Location Units*B. Repair ProceduresVI. REPLACEMENT PARTSA. Returned Merchandise Authorization (RMA) Procedures All Port-A-Co
PORT-A-COOL® Hazardous Location Units*APPENDIX AA-1Port-A-Cool®TEMPERATURE OUTPUT CHARACTERISTICS10% TO 25% RELATIVE HUMIDITYDRY BULBTemp. °C Temp.
PORT-A-COOL® Hazardous Location Units*A-2APPENDIX APort-A-Cool®TEMPERATURE OUTPUT CHARACTERISTICS30% TO 45% RELATIVE HUMIDITYDRY BULBTemp. °C Temp.
PORT-A-COOL® Hazardous Location Units*DRY BULBTemp. °C Temp. °F23.9 7526.7 8029.4
PORT-A-COOL® Hazardous Location Units*Port-A-Cool®TEMPERATURE OUTPUT CHARACTERISTICS70% TO 75% RELATIVE HUMIDITYAPPENDIX A WET BULB TEMPERATUREDRY
PORT-A-COOL®Evaporative Cooling UnitsOWNERS MANUAL I. INTRODUCTION A. What is evaporative cooling? B. Humidity and Evaporative Cooling. C.
PORT-A-COOL® Hazardous Location Units*I. INTRODUCTIONThe PORT-A-COOL® unit is a fully self-contained, portable, high efficiency evaporative cooler t
PORT-A-COOL® Hazardous Location Units*The following table demonstrates the BTU’s removed from the air based on a given amount of water evaporated in
PORT-A-COOL® Hazardous Location Units*C. Evaporative Cooling and the PORT-A-COOL® unit.The PORT-A-COOL® unit is the state-of-the-art, high effi
PORT-A-COOL® Hazardous Location Units*I. SETUPA. Unpacking the PORT-A-COOL@ unit.The PORT A-COOL HAZARDOUS LOCATION MODELS (PAC2K36EP and PAC2K48EP)
PORT-A-COOL® Hazardous Location Units*Water supply inlet pressure should be limited to 50 psi maximum.The cooling pads may now be replaced by revers
II. OPERATING PROCEDURESA. Placement of the PORT-A-COOL@ unit.PORT-A-COOL@ units should be used in well-ventilated areas only.There are three primary